FAULT TRACING vacon • 101
24-hour support: +358 (0)40 837 1150 • Email: vacon@vacon.com
Problem detected in encoder signals.
Sub code in T.14:
S1 =Encoder 1 channel A is missing
S2 =Encoder 1 channel B is missing
S3 =Both enc. 1 channels are missing
S4 =Encoder reversed
S5 =Encoder board missing
S6 = Serial communication fault
S7 = Channel A/Channel B mismatch
S8 = Resolver/Motor pole pair mismatch
S9 = Missed start angle
Check encoder channel connections.
Check the encoder board.
(different type)
Option board or power unit changed.
New device of different type or different
rating than the previous one.
Set the option board parameters again if
option bard changed. Set converter
parameters again if power unit changed.
(different type)
Option board of different type added.
Set the option board parameters again.
application
A division by zero has occurred in the
application program.
Contact your distributor. If you are
application programmer check the
application program.
I
in
< 4mA (sel.
signal range 4
to 20 mA)
Current at the analogue input is < 4mA.
control cable is broken or loose
signal source has failed
Check the current loop circuitry.
communication
fault
The connection between the control
keypad and the frequency converter is
broken.
Check keypad connection and possible
keypad cable.
The data connection between the
fieldbus Master and the fieldbus board
is broken
If installation is correct contact the
nearest Vacon distributor.
Defective option board or slot
Contact the nearest Vacon distributor.
temp. fault
Temperature limit values set for the
PT100 board parameters have been
exceeded
Find the cause of temperature rise
Table 11-2. Fault codes