18 • vacon TECHNICAL DATA
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
4.2 Technical data
connection
in
380...500V;525...690V; –10%…+10% (regenerative drives)
connection
current
Ambient temperature max. +40°C
See Table 4-1 and Table 4-3.
High: 1.5 x IH (1 min/10 min), Low: 1.1 x IL (1 min/10
min)
0…320 Hz; (higher with special SW)
characteristics
Open Loop Vector Control (5-150% of base speed):
speed control 0.5%, dynamic 0.3%sec, torque lin. <2%,
torque rise time ~5 ms
Closed Loop Vector Control (entire speed range):
speed control 0.01%, dynamic 0.2%sec, torque lin. <2%,
torque rise time ~2 ms
NX_6:
1…6 kHz; Factory default 3.6 kHz *
1…6 kHz; Factory default 1.5 kHz *
Analogue input
Panel reference
Resolution 0.1% (10-bit), accuracy ±1%
Resolution 0.01 Hz
conditions
temperature
no dripping water
- chemical vapours
mechanical particles
IEC 721-3-3, unit in operation, class 3C2
IEC 721-3-3, unit in operation, class 3S2
Cabinet surface treatment
textured powder-coating
100% load capacity (no derating) up to 1,000 m
1-% derating for each 100m above 1000; max. 3000m
(690V max 2000m)
EN50178/EN60068-2-6
Displacement amplitude 0.25 mm (peak) at 5…31 Hz
Max acceleration 1 G at 31…150 Hz
Use anti-vibration mountings under the drive if extra
vibration resistance is required
EN50178, EN60068-2-27
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in package)
IP21/NEMA1 standard in entire kW/HP range
IP54/NEMA12 option in entire kW/HP range
(Continues on next page)
*The rated currents in given ambient temperatures are achieved only when the switching frequency is
equal to or less than the factory default. Thermal management might reduce the switching frequency.