44 • vacon CABLING AND CONNECTIONS
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
6
6.2.6.2 12-pulse drives
Frame Type
I
L
[A]
Bussmann / Ferraz
Shawmut fuse type
Fuse I
n
[A]
Mains and motor
cable
1)
[mm
2
]
No. of
supply
cables
No. of
motor
cables
FR10
NX0385 5
385
170M5813 (3 pcs)
NH2UD69V500PV (3 pcs)
700/500
Cu: 2*(3*120+70)
Al: 2*(3*185Al+57Cu)
Even/Odd Even/Odd
NX0460 5 460
170M5813 (3 pcs)
NH2UD69V500PV (3 pcs)
700/500
Cu: 2*(3*150+70)
Al: 2*(3*240Al+72Cu)
Even/Odd Even/Odd
NX0520 5 520
170M5813 (3 pcs)
NH2UD69V500PV (3 pcs)
700/500
Cu: 2*(3*185+95)
Al: 2*(3*300Al+88Cu)
Even/Odd Even/Odd
FR11
NX0590 5 590
170M5813 (6 pcs)
NH2UD69V700PV (6 pcs)
700
Cu: 2*(3*240+120)
Al: 4*(3*120Al+41Cu)
Even Even/Odd
NX0650 5 650
170M5813 (6 pcs)
NH2UD69V700PV (6 pcs)
700
Cu: 4*(3*95+50)
Al: 4*(3*150Al+41Cu)
Even Even/Odd
NX0730 5 730
170M5813 (6 pcs)
NH2UD69V700PV (6 pcs)
700
Cu: 4*(3*120+70)
Al: 4*(3*185Al+57Cu)
Even Even/Odd
FR12
NX0820 5 820
170M8547 (6 pcs)
NH3UD69V1000PV (6 pcs)
1250/1000
Cu: 4*(3*150+70)
Al: 4*(3*185Al+57Cu)
Even Even
NX0920 5 920
170M8547 (6 pcs)
NH3UD69V1000PV (6 pcs)
1250/1000
Cu: 4*(3*150+70)
Al: 4*(3*240Al+72Cu)
Even Even
NX1030 5 1030
170M8547 (6 pcs)
NH3UD69V1000PV (6 pcs)
1250/1000
Cu: 4*(3*185+95)
Al: 4*(3*300Al+88Cu)
Even Even
FR13
NX1150 5 1150 No additional drive fuses needed
Cu: 4(3*240+170)
Al: 6*(3*185Al+57Cu)
Even Even/Odd
NX1300 5 1300 No additional drive fuses needed
Cu: 6(3*1
50+70)
Al: 6*(3*240Al+72Cu)
Even Even/Odd
NX1450 5 1450 No additional drive fuses needed
Cu: 6(3*185+95)
Al: 6*(3*240Al+72Cu)
Even Even/Odd
FR14
NX1770 5 1770 No additional drive fuses needed
Cu: 6*(3*240+120)
Al: 8*(3*240Al+72Cu)
Even Even
NX2150 5 2150 No additional drive fuses needed
Cu: 8*(3*185+95)
Al: 8*(3*300Al+88Cu)
Even Even
Table 6-3. Cable and fuse sizes for Vacon NX_5, 12-pulse supply
1)
Based on correction factor 0.7. Cables are laid on a cable ladder side by side, three ladders on top of each other. Ambient
temperature is 30°C (86°F). EN60204-1 and IEC 60364-5-523.